Experimental study on heat transfer performance of filler-plate combination evaporative coolers
|更新时间:2025-09-28
|
Experimental study on heat transfer performance of filler-plate combination evaporative coolers
Thermal Power GenerationVol. 43, Issue 3, Pages: 65-70(2014)
作者机构:
华东理工大学承压系统与安全教育部重点实验室
作者简介:
基金信息:
DOI:
CLC:TQ051.5
Published:2014
稿件说明:
移动端阅览
SHI Zhongjing, SHI Yunyi, QIAN Tailei, et al. Experimental study on heat transfer performance of filler-plate combination evaporative coolers[J]. Thermal power generation, 2014, 43(3): 65-70.
DOI:
SHI Zhongjing, SHI Yunyi, QIAN Tailei, et al. Experimental study on heat transfer performance of filler-plate combination evaporative coolers[J]. Thermal power generation, 2014, 43(3): 65-70.DOI:
Experimental study on heat transfer performance of filler-plate combination evaporative coolers
A new type filler-plate combination evaporative cooler is designed.The fillers and heat exchanger plates which overlap together are used as heat exchanger components.Thus
the heat transfer is enhanced by mixed strengthened cooling between the fillers and the plates.Moreover
a plate evaporator cooler performance test system was built to study the influence of spray density
air volume
ambient wet bulb temperature and flier layer on plate evaporator cooler's heat transfer property.The results show that:increasing the air volume and spray water flow can improve cooling efficiency of the evaporative cooler
and there is an optimum spray density;during the experiment
when the air wet bulb temperature rises by 9℃
the outlet temperature of working fluid in plates increases by 2℃ and the cooling efficiency is improved by 3%;with the same spray density or air flow
the heat density increases with the filler layer thickness.