A steam parameter control strategy for shaft sealing system without spray attemperator and its application
|更新时间:2025-09-28
|
A steam parameter control strategy for shaft sealing system without spray attemperator and its application
Thermal Power GenerationVol. 43, Issue 7, Pages: 149-152(2014)
作者机构:
河南省电力公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2014
稿件说明:
移动端阅览
LIANG Zhengyu, LIU Zongxu, JIANG Lingfeng. A steam parameter control strategy for shaft sealing system without spray attemperator and its application[J]. Thermal power generation, 2014, 43(7): 149-152.
DOI:
LIANG Zhengyu, LIU Zongxu, JIANG Lingfeng. A steam parameter control strategy for shaft sealing system without spray attemperator and its application[J]. Thermal power generation, 2014, 43(7): 149-152.DOI:
A steam parameter control strategy for shaft sealing system without spray attemperator and its application
摘要
针对某西门子660MW机组轴封系统无喷水减温装置和备用汽源的特点
提出了一种新型蒸汽参数控制策略
即通过对供汽调节阀与溢流调节阀的耦合调节
控制轴封蒸汽压力和采用蒸汽减温代替喷水减温等
在各个工况下实现了对轴封蒸汽参数的自动控制。通过与原控制策略的对比
对存在的控制缺陷给出了改进建议。
Abstract
Against the characteristics of a Siemens 660MW unit's shaft sealing system which is not equipped with spray attemperator and redundant steam supply
a novel control strategy was put forward.On the basis of coupling pressure regulation with steam supply valve and overflow valve as actuators
the control strategy adopted steam desuperheating instead of spray desuperheating
which achieved automatic control of shaft sealing steam parameters under each working condition.By comparison with the original control strategy
some suggestions were proposed against the defects of existing Siemens control strategy.