Experimental study on heat transfer performance of ethanol OHP and water OHP
|更新时间:2025-09-28
|
Experimental study on heat transfer performance of ethanol OHP and water OHP
Thermal Power GenerationVol. 43, Issue 4, Pages: 38-42(2014)
作者机构:
南京工业大学能源学院
作者简介:
基金信息:
DOI:
CLC:TK124;TK172.4
Published:2014
稿件说明:
移动端阅览
ZHU Jing, ZHANG Hong, SU Lei. Experimental study on heat transfer performance of ethanol OHP and water OHP[J]. Thermal power generation, 2014, 43(4): 38-42.
DOI:
ZHU Jing, ZHANG Hong, SU Lei. Experimental study on heat transfer performance of ethanol OHP and water OHP[J]. Thermal power generation, 2014, 43(4): 38-42.DOI:
Experimental study on heat transfer performance of ethanol OHP and water OHP
摘要
通过实验研究了加热功率变化时
铜-水和铜-乙醇振荡热管的传热性能及其壁温波动特征。结果表明:正常工作时
水热管均温性优于乙醇热管
传热热阻较乙醇热管小;低加热功率下
随加热功率增加
水热管壁温波动形式存在明显的转变
而乙醇热管无类似现象;高加热功率下
水热管热阻不断增大
而乙醇热管内局部出现工质过热现象
但依然能保持稳定的传热性能;温度波动振幅及频率大、波动稳定且均匀的热管传热性能较好。
Abstract
The heat transfer performance and wall temperature variation of copper-water oscillating heat pipe(OHP)and copper-ethanol OHP at different heating powers was experimentally investigated.The results show that
under normal conditions
the temperature difference between evaporation and condensation section of water OHP is smaller than that of the ethanol OHP
and the heat transfer resistance of water OHP is also lower.Comparison of wall temperature fluctuation curves between the two OHPs indicates that
at low heating powers
there are clear shifts in the water OHP's wall temperature
with an increase in heating power;however
there's no such a situation in the ethanol OHP;at high heating powers
the heat transfer resistance of water OHP increases continuously
while inside local parts of the ethanol OHP
overheating occurs in working fluid
but the heat transfer performance maintains stable.Finally
the experiments imply that
the heat pipes with large temperature fluctuation amplitude
high vibration frequency
and stable and uniform fluctuation have better heat transfer performance.