Cause analysis and treatment of boiler water abnormity in a 300MW unit
|更新时间:2025-09-28
|
Cause analysis and treatment of boiler water abnormity in a 300MW unit
Thermal Power GenerationVol. 43, Issue 5, Pages: 139-141(2014)
作者机构:
1. 西安热工研究院有限公司
2. 神华神东电力有限责任公司新疆米东热电厂
作者简介:
基金信息:
DOI:
CLC:TM621.8
Published:2014
稿件说明:
移动端阅览
LIU Wei, MA Zhijing, JIA Rong. Cause analysis and treatment of boiler water abnormity in a 300MW unit[J]. Thermal power generation, 2014, 43(5): 139-141.
DOI:
LIU Wei, MA Zhijing, JIA Rong. Cause analysis and treatment of boiler water abnormity in a 300MW unit[J]. Thermal power generation, 2014, 43(5): 139-141.DOI:
Cause analysis and treatment of boiler water abnormity in a 300MW unit
The conductivity and pH value of boiler water in No.1unit of Midong Thermal Power Plant were over standard.So the water wall tubes suffered the risk of alkaline corrosion and boiler water concentrate corrosion.Detection finds a larger number of free sodium hydroxide appears in the boiler water.This is because the heat-supply network drain which is used as the feed water supplement water was polluted by leakage of circulating water of district heating system heater. The check valve between the steam separated from continuous blow-down flash vessel and the deaerator had some defects
leading to invalid blow down
so the boiler water were over concentrated
a larger number of free sodium hydroxide appeared in the boiler water
resulting in boiler water abnormality eventually.Finally