Modification of acid value measuring standard for oil used in electric power industry
The reason for poor reproducibility of the results obtained by two test methods for electric oil acid value detection
GB/T 264—1983(Petroleum products—Determination of acid number)and GB/T 28552—2012(Determination of acid number in transformer and turbine oils in service by BTB method(BTB method))
was analyzed.It finds out that
when the acid value of the oil is relatively high
within the color changing range of the indicator in above two standards
the pH value of the solution varied little with the alkali liquor volume
and no titration jump occurred
so the solution's color had no sudden change
resulting in difficult in judging the titration end-point.It suggests that
when using alkali bule 6Bas the indicator
the titration end-point be the point when blue color disappears;when using BTB as the indicator
the titration end-point be the point when yellow changes for yellowish-green;for the oil with heavy color which is difficult to determine the titration end-point
the sample weight should be reduced.After the above modifications
the poor reproducibility of the results has been greatly improved
which is beneficial to the electric oil quality supervision.