Experimental study on dynamic characteristics of direct air-cooling system in a 600MW unit
|更新时间:2025-09-28
|
Experimental study on dynamic characteristics of direct air-cooling system in a 600MW unit
Thermal Power GenerationVol. 43, Issue 3, Pages: 76-78(2014)
作者机构:
1. 内蒙古霍煤鸿骏铝电公司
2. 西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2014
稿件说明:
移动端阅览
LIU Wenhua, LI Gaochao, YAN Yongqiang, et al. Experimental study on dynamic characteristics of direct air-cooling system in a 600MW unit[J]. Thermal power generation, 2014, 43(3): 76-78.
DOI:
LIU Wenhua, LI Gaochao, YAN Yongqiang, et al. Experimental study on dynamic characteristics of direct air-cooling system in a 600MW unit[J]. Thermal power generation, 2014, 43(3): 76-78.DOI:
Experimental study on dynamic characteristics of direct air-cooling system in a 600MW unit
The effects of factors like air-cooling fan's frequency
unit load and ambient temperature on dynamic characteristics of the direct air-cooling system in a 600MW unit was experimentally studied.The results showed that
the lower the air-cooling fan's frequency
the higher the variation speed of turbine back pressure against the ambient temperature;with a constant air-cooling fan's frequency
the variation rate of turbine pressure against the unit load increased/decreased with the ambient temperature;at a constant ambient temperature
the variation rate of turbine back pressure against the unit load showed an opposite change trend with the air-cooling fan's frequency; when the unit load was kept constant
the lower ambient temperature
the less effect of air-cooling fan's frequency on the turbine back pressure.