Lectotype of axial flow forced draft fan with adjustable rotating blades for a 600MW unit:margin analysis and energy saving reconstruction
|更新时间:2025-09-28
|
Lectotype of axial flow forced draft fan with adjustable rotating blades for a 600MW unit:margin analysis and energy saving reconstruction
Thermal Power GenerationVol. 43, Issue 4, Pages: 15-20(2014)
作者机构:
国电科学技术研究院
作者简介:
基金信息:
DOI:
CLC:TH443
Published:2014
稿件说明:
移动端阅览
NING Xinyu, WANG Shuangtong. Lectotype of axial flow forced draft fan with adjustable rotating blades for a 600MW unit:margin analysis and energy saving reconstruction[J]. Thermal power generation, 2014, 43(4): 15-20.
DOI:
NING Xinyu, WANG Shuangtong. Lectotype of axial flow forced draft fan with adjustable rotating blades for a 600MW unit:margin analysis and energy saving reconstruction[J]. Thermal power generation, 2014, 43(4): 15-20.DOI:
Lectotype of axial flow forced draft fan with adjustable rotating blades for a 600MW unit:margin analysis and energy saving reconstruction
摘要
通过调研30台600 MW级机组动叶可调轴流式送风机的设备选型及实际运行状况
发现部分送风机存在选型偏大、电机容量与风机容量不匹配等问题
这会增加机组的初期投资
降低风机实际运行效率
增加电耗。建议将送风机选型的流量裕度控制在5%左右
风机电机功率控制在1 500kW以内
并对裕量偏大的送风机进行降速降容节能改造。
Abstract
According to survey of equipment code and practical operation state of axial-flow forced draft fan with adjustable rotating blades in some 600MW units
such problems as overlarge type selection
mismatch between the electric motor capacity and the fan capacity were found
which may increase the unit initial investment
decrease the actual operation efficiency of the axial-flow forced draft fan
and raise the electricity consumption.It suggested that the flow margin during type selection of the forced draft fan should be controlled at about 5%
and the motor power be within 1 500kW.Besides
the economical benefit comparison between capacity-decreasing speedreduction retrofit and frequency conversion retrofit was performed.For reconstruction of the axial flow forced draft fan
the capacity-decreasing speed-reducing retrofit was suggested.