Energy consumption analysis on extraction steam heating and circulating water-water source heat pump heating
|更新时间:2025-09-28
|
Energy consumption analysis on extraction steam heating and circulating water-water source heat pump heating
Thermal Power GenerationVol. 43, Issue 3, Pages: 14-20(2014)
作者机构:
上海电力学院能源与机械工程学院
作者简介:
基金信息:
DOI:
CLC:TU83
Published:2014
稿件说明:
移动端阅览
LIU Jiantao, REN Jianxing, YANG Yongwen, et al. Energy consumption analysis on extraction steam heating and circulating water-water source heat pump heating[J]. Thermal power generation, 2014, 43(3): 14-20.
DOI:
LIU Jiantao, REN Jianxing, YANG Yongwen, et al. Energy consumption analysis on extraction steam heating and circulating water-water source heat pump heating[J]. Thermal power generation, 2014, 43(3): 14-20.DOI:
Energy consumption analysis on extraction steam heating and circulating water-water source heat pump heating
摘要
以300MW机组为例
分析计算了火电厂抽汽供热与循环水-水源热泵供热2种方式的特点和能耗。结果表明
当水源热泵系统的能效比(COP)大于5.03时
循环水-水源热泵供热方式的节能效果较好。目前水源热泵在实际运行时COP为4.5~5.5
其供热能耗与抽汽供热相当。
Abstract
Taking a 300 MW unit as the example
the characteristics and energy consumption of two heating approaches
extraction steam heating and circulating water-water source heat pump(CW-WSHP)heating
were investigated.The results show that
when the coefficient of performance(COP)of the water source heat pump system is larger than 5.03
the CW-WSHP heating method has better energy saving effect than the extraction steam heating method.Due to limitation of the technology
the actual COPof the current water source heat pump is about 4.5to 5.5. Therefore
the energy consumption of the CW-WSHP heating method is basically equivalent to that of the extraction steam heating method.