Fuzzy self-adaptive Smith cascade control system for spraying ammonia in SCR reactors
|更新时间:2025-09-28
|
Fuzzy self-adaptive Smith cascade control system for spraying ammonia in SCR reactors
Thermal Power GenerationVol. 43, Issue 8, Pages: 147-150(2014)
作者机构:
1. 西安热工研究院有限公司
2. 西安电力高等专科学校电力工程系
作者简介:
基金信息:
DOI:
CLC:X773
Published:2014
稿件说明:
移动端阅览
LI Gang, HU Sen, WU Baohui. Fuzzy self-adaptive Smith cascade control system for spraying ammonia in SCR reactors[J]. Thermal power generation, 2014, 43(8): 147-150.
DOI:
LI Gang, HU Sen, WU Baohui. Fuzzy self-adaptive Smith cascade control system for spraying ammonia in SCR reactors[J]. Thermal power generation, 2014, 43(8): 147-150.DOI:
Fuzzy self-adaptive Smith cascade control system for spraying ammonia in SCR reactors
By analyzing the cause of large delay in ammonia spraying control in SCR reactor
the fuzzy self-adaptive Smith cascade control system was applied.In this method
the Smith cascade controller is used to predictively control the spraying ammonia flow and the fuzzy rules are used to adjust the PID parameters online.So the controller can adapt to changes of the control object effectively.Comparison between the fuzzy self-adaptive Smith cascade control system and the conventional PID cascade controller was carried out by simulation testing.The results show that
the control effectiveness of this Smith cascade controller was superior to that of the conventional PID cascade controller
and good control performance can be maintained when the model of control object changed
indicating the Smith cascade controller has strong adaptability.