Effect of diffuser's outlet structure on exhaust hood's aerodynamic performance
Thermal Power GenerationVol. 43, Issue 8, Pages: 131-135(2014)
作者机构:
1. 华北电力大学电站设备状态检测与控制教育部重点实验室
2. 国电山东石横发电厂
3. 国电蓬莱发电有限公司
作者简介:
基金信息:
DOI:
CLC:TM311
Published:2014
稿件说明:
移动端阅览
ZHOU Lanxin, YANG Xinjian, CHEN Jian, et al. Effect of diffuser's outlet structure on exhaust hood's aerodynamic performance[J]. Thermal power generation, 2014, 43(8): 131-135.
DOI:
ZHOU Lanxin, YANG Xinjian, CHEN Jian, et al. Effect of diffuser's outlet structure on exhaust hood's aerodynamic performance[J]. Thermal power generation, 2014, 43(8): 131-135.DOI:
Effect of diffuser's outlet structure on exhaust hood's aerodynamic performance
Numerical simulation on exhaust hood model with different inner guide ring angles and widths at outlet of the diffuser was performed
by using the Fluent software.The results show that:the optimal inner guide ring angleβwas 75°
with which the pressure loss of the exhaust hood reduced by 41.2Pa
compared with theβ=0°condition;the optimal outlet width d was 1 250 mm
with which the pressure loss dropped by 16.8Pa
compared with the d=1 100 mm condition;adding a series of baffles at the exhaust hood downstream can divide the vortex with heavier intensity into multiple weaker vortexes
thus to control the strength and range of the vortexes.After the dampers were installed
the pressure loss decreased by27.8Pa.Application of the retrofitted exhaust hood on a 600 MW unit indicated that
the pressure loss of the exhaust hood dropped by 69 Pa
and the effective specific enthalpy drop increased by 0.08%.