Organic controlling indexes in power plant water-steam systems
Because the water-steam system is more vulnerable to chlorine
sulphur
phosphorus and other components in organics
it is important for power plants to control the content of organics in water and steam.However
the conventional determination of organics(TOC)only represents the carbon content in organics
excluding chlorine
sulfur and other more corrosive elements.Therefore
a more advanced determination method containing all of the components(TOCi)in organics was proposed.The actual application proved the TOCi can be more exact in organic determination.It is suggested the TOCi be applied instead of the TOC to evaluate the organics content in water for power plants.