摘要
为了节能和提高能源利用率
锅炉风烟系统采用了3台电动引风机
从而出现了常规双引风机的平衡偏置控制策略不适用于炉膛压力控制
且无法实现3台引风机之间的平衡控制的问题。对此
通过在Ovation DCS上开发IDFBALANCER宏模块
很好地解决了3台引风机间的平衡控制问题
并且提高了在改变自动控制方式的引风机数量时
炉膛压力调节回路的自适应能力。
Abstract
To enhance the energy utilization efficiency
three motor-driven induced-draft fans(IDF)are applied
causing problem taht the balance bias control strategy of the conventional double-IDF is not applicable to furnace pressure control.Moreover
balance control of the three IDFs can not be realized.Thus
by developing macro module IDFBALANCER in Ovtaion DCS
the balance control problem among the three IDFs was well solved
and the control loop's adaptive ability with different auto IDF's numbers was enhanced.
WET FLUE GAS DESULFURATION TECHNOLOGY WITHOUT BOOSTER FAN FOR 135MW UNIT
ENERGY-SAVING RETROFIT OF INDUCED DRAFT FANS IN GUODIAN SHIZUISHAN POWER-GENERATION CO LTD, NING XIA HUI AUTONOMOUS REGION
CAUSE ANALYSIS ABOUT SOMEWHAT LARGER ELECTRIC CURRET OF INDUCED DRAFT FAN FOR ONE BOILER
ANALYSIS OF FEASIBILITY FOR RETROFITTING INDUCED DRAFT FAN INTO A LOW SPEED ONE
FURNACE PRESSURE CONTROL BASED ON COMBINED REGULATION OF HYDRAULIC COUPLING AND STATIONARY BLADES IN INDUCED DRAFT FAN AND APPLICATION OF THE CONTROL SYSTEM