Optimization of air flow field for direct air cooling units
|更新时间:2025-09-28
|
Optimization of air flow field for direct air cooling units
Thermal Power GenerationVol. 44, Issue 3, Pages: 81-86(2015)
作者机构:
1. 华电新疆发电有限公司昌吉热电厂
2. 华北电力大学能源动力与机械工程学院
作者简介:
基金信息:
DOI:
CLC:TK264.11
Published:2015
稿件说明:
移动端阅览
SHUI Haibo, WANG Xiaolong, ZHANG Tao, et al. Optimization of air flow field for direct air cooling units[J]. Thermal power generation, 2015, 44(3): 81-86.
DOI:
SHUI Haibo, WANG Xiaolong, ZHANG Tao, et al. Optimization of air flow field for direct air cooling units[J]. Thermal power generation, 2015, 44(3): 81-86.DOI:
Optimization of air flow field for direct air cooling units
摘要
直接空冷系统空冷单元空气流场具有明显的旋转上升特点
且呈中心对称分布
使空冷单元翅片管束的冷却空气流量分配极不均匀
翅片管束传热面利用效率低
空冷凝汽器流动传热性能差。对此
利用CFD软件
对直接空冷单元内部的空气动力学特性进行研究
发现
由于风机出口流通面积的突变
在空冷单元底部形成了流动死区和涡流
在单元中心形成了严重的回流
导致流动阻力增加
阻碍了风机出口冷却空气向翅片管束方向的顺利流动。为此
提出4种导流方案
对4种导流方案的空冷单元热力性能进行研究。结果表明
经过空冷单元内冷却空气导流后
空气流场得到优化
管束表面流量和温度场更为均匀
空冷单元流动传热性能得到了改善。4种导流方案中
方案3的效果最为显著。
Abstract
The air flow field of air cooling unit in direct air cooling systems has dramatic spiral trend and is centrosymmetric distributed
resulting in a very uneven distribution of cooling air volume in finned tube bundles
a really low utilization efficiency of the heating surface of finned tubes and quite poor flow and heat transfer performance of air cooled condenser. Thus
the CFD software was applied to investigate the dynamic characteristics of air flow field inside the direct air cooling unit. It finds that due to sudden change of flow area at the fan outlet
flow dead zone and vortexes form at the air cooling unit bottom and serious reflux occurs in the unit center
causing an increase in flow resistance
which impedes the cooling air to flow from the fan outlet toward the finned tube bundles. Therefore
four flow guidance schemes were put forward and thermal performance of the air cooling unit in these four schemes were analyzed. The results show that
after guidance of the cooling air inside the air cooling unit
the air flow field is optimized
the bundles' surface flow and temperature field are more uniform and the flow and heat transfer property of the air cooling unit are significantly improved.