Applicability analysis on lithium chloride saltwater cooling system in a thermal power plant
|更新时间:2025-09-28
|
Applicability analysis on lithium chloride saltwater cooling system in a thermal power plant
Thermal Power GenerationVol. 44, Issue 5, Pages: 76-80(2015)
作者机构:
河海大学水利水电学院
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2015
稿件说明:
移动端阅览
WANG Zhengming, XIA Lin, CHEN Yongji. Applicability analysis on lithium chloride saltwater cooling system in a thermal power plant[J]. Thermal power generation, 2015, 44(5): 76-80.
DOI:
WANG Zhengming, XIA Lin, CHEN Yongji. Applicability analysis on lithium chloride saltwater cooling system in a thermal power plant[J]. Thermal power generation, 2015, 44(5): 76-80.DOI:
Applicability analysis on lithium chloride saltwater cooling system in a thermal power plant
Based on the theory of pressure difference in wet cooling tower
a 600 MW unit power plant was taken as an example to analyze the change rules of water-saving amount and power reduction of lithium chloride(LiCl)saltwater cooling system against varying of such factors as the LiCl mass fraction
weather condition and recirculation cooling water amount.The influence of these boundary conditions on economic benefits of the saltwater cooling system was also discussed.The result shows
the lithium chloride mass fraction should not get too high.If it is relatively high
the recirculation cooling water amount should be increased to enhance the economic benefit of the saltwater cooling system.Moreover
economic benefit of the saltwater cooling system decreased with the increasing environmental relative humidity and dry-bulb temperature.Therefore
the dry air and low temperature weather condition or area is more favorable for the saltwater cooling system.