Dynamic correction methods for temperature measurement by telescopic armoured temperature sensor
|更新时间:2025-09-28
|
Dynamic correction methods for temperature measurement by telescopic armoured temperature sensor
Thermal Power GenerationVol. 44, Issue 7, Pages: 107-110(2015)
作者机构:
东南大学能源与环境学院
作者简介:
基金信息:
DOI:
CLC:TP212
Published:2015
稿件说明:
移动端阅览
WANG Lei, YANG Jianming. Dynamic correction methods for temperature measurement by telescopic armoured temperature sensor[J]. Thermal power generation, 2015, 44(7): 107-110.
DOI:
WANG Lei, YANG Jianming. Dynamic correction methods for temperature measurement by telescopic armoured temperature sensor[J]. Thermal power generation, 2015, 44(7): 107-110.DOI:
Dynamic correction methods for temperature measurement by telescopic armoured temperature sensor
摘要
套管式铠装温度传感器因热扩散系数低
温度敏感元件的温度变化滞后于被测介质
从而产生很大的动态测量误差。对此
采用逆导热问题求解的顺序函数法
基于温度传感器输出随时间的变化
对套管式铠装温度传感器进行动态测量
反演出介质与传感器表面的换热热流
由此计算出介质温度。数值模拟显示:基于顺序函数法
对套管式铠装温度传感器做动态校正
通过参数优化
能较快地跟踪被测介质温度的变化
大大缩短了温度动态测量的响应时间。
Abstract
Due to low thermal diffusivity
the temperature of armoured sensor sensitive parts lags behind that of the measured medium
resulting in a large dynamic measurement error.Thus
the sequential function method based on reverse heat-conduction problem was applied to dynamically measure the temperature sensors
on the basis of the sensor output variation against time.Then the heat flux between surface and medium can be estimated
and the medium temperature can be calculated.The simulation results show that
the temperature measurement can be corrected dynamically by the sequential function method.Through parameter optimization
the temperature change of the measured medium can be traced quickly
so the response time of dynamic temperature measurement is sharply shortened.