Exergy efficiency analysis of heat pump heating system recycling waste heat from circulating water
|更新时间:2025-09-28
|
Exergy efficiency analysis of heat pump heating system recycling waste heat from circulating water
Thermal Power GenerationVol. 44, Issue 6, Pages: 106-110(2015)
作者机构:
西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TK115
Published:2015
稿件说明:
移动端阅览
ZHANG Pengfei, FU Chang, WANG Weifeng, et al. Exergy efficiency analysis of heat pump heating system recycling waste heat from circulating water[J]. Thermal power generation, 2015, 44(6): 106-110.
DOI:
ZHANG Pengfei, FU Chang, WANG Weifeng, et al. Exergy efficiency analysis of heat pump heating system recycling waste heat from circulating water[J]. Thermal power generation, 2015, 44(6): 106-110.DOI:
Exergy efficiency analysis of heat pump heating system recycling waste heat from circulating water
this paper experimentally analyzed the energy saving effect of heat pump heating system recycling waste heat from circulating water in a subcritical 330 MW indirect air cooling unit with extraction heating.The results show that
with a relatively constant main steam flow rate and heat load
the total steam extraction rate under heat pump heating condition was dramatically lower than that under single heat net heating condition.The coefficient of performance(COP)of the heat pump in this unit is 1.631
and the exergy efficiency and generator power of the heating system increased by 8%and 10.729 MW respectively after the heat pump was applied.Assuming the annual average standard coal consumption of the unit for power generation is 330g/(kW ·h)and the annual heat supply time is3 816 h
the unit can save standard coal by 13 512 tevery year.