According to such characteristics of the controlled object as large inertia
large delay and nonlinearity
a model free adaptive control and PED(MFAC-PID)cascade control system with dead zone was designed
on the basis of anti interference of PID control and strong adaptability of model free adaptive control(MFAC)to inertia and delay system.Moreover
taking the selective non-catalytic reduction(SNCR)flue gas denitration system in Midong Thermal Power Plant as the object
the system simulation model was established
and the MATLAB software was applied to compare the two control methods.The results show that
under conditions with step disturbance and model mismatch
the MFAC-PID cascade control system with dead zone has smaller overshoot and shorter settling time than the conventional PID cascade control system.Under unit load disturbance condition
the MFAC-PID cascade control system with dead zone has very small fluctuation.Therefore
the MFAC-PID cascade control system with dead zone can better adapt to the changes of object parameters