Model-based soft measurement for coal calorific value and BTU correction method
Thermal Power GenerationVol. 44, Issue 11, Pages: 43-47(2015)
作者机构:
贵州电力试验研究院
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2015
稿件说明:
移动端阅览
ZHANG Ruifeng, AN Bo, LI Xiaojun, et al. Model-based soft measurement for coal calorific value and BTU correction method[J]. Thermal power generation, 2015, 44(11): 43-47.
DOI:
ZHANG Ruifeng, AN Bo, LI Xiaojun, et al. Model-based soft measurement for coal calorific value and BTU correction method[J]. Thermal power generation, 2015, 44(11): 43-47.DOI:
Model-based soft measurement for coal calorific value and BTU correction method
The conventional BTU correction logic has disadvantages of low capability of anti-load jamming and poor stability.Against this problem
the conventional BTU correction method and the one for modelbased soft measurement of coal calorific value were analyzed.Moreover
the operation data of a subcritical600 MW unit were used to carry out experimental verification for this BTU correction method for modelbased soft measurement of coal calorific value.The results show that
using the simplified nonlinear dynamic model of unit load-throttle pressure
the calorific value of coal was calculated
which can eliminate the effects of fuel flow variation and opening degree variation of turbine regulation valves on the coordinated control system.By employing the low-pass filter
the operation frequency of the BTU correction logic can be lower than that of the coordinated control system and the close-loop stability of all system can be guaranteed.The practical applications indicate this method has better dynamic and static stability
and the antijamming ability is higher.The calculation precision and lag time can satisfy the local demand and can be suitable for thermal power units with frequently changed generation load.