Retrofitting of reheaters in 300MW and 600MW unit pulverized coal boilers
|更新时间:2025-09-28
|
Retrofitting of reheaters in 300MW and 600MW unit pulverized coal boilers
Thermal Power GenerationVol. 45, Issue 1, Pages: 126-131(2016)
作者机构:
1. 太原理工大学电气与动力工程学院
2. 山西格盟国际能源有限公司
作者简介:
基金信息:
DOI:
CLC:TM621.2
Published:2016
稿件说明:
移动端阅览
JIA Li, XIAO Faqi, CAI Xinchun, et al. Retrofitting of reheaters in 300MW and 600MW unit pulverized coal boilers[J]. Thermal power generation, 2016, 45(1): 126-131.
DOI:
JIA Li, XIAO Faqi, CAI Xinchun, et al. Retrofitting of reheaters in 300MW and 600MW unit pulverized coal boilers[J]. Thermal power generation, 2016, 45(1): 126-131.DOI:
Retrofitting of reheaters in 300MW and 600MW unit pulverized coal boilers
For a 600 MW and two 300 MW units pulverized coal boilers
the burners tilt down
and the temperature in reheater and the amount of desuperheater spray exceed their design value.Too much heating surface area caused heat deviation in the reheater was considered as the major reason
according to the coal characteristics(low heat calorific value
high moisture and ash content).Therefore
it is proposed to cut part of the heating area.The actual operation results show that the desuperheater spray amount decreased markedly and the burner tilt can also be placed in a horizontal position at low loads after the retrofitting.The retrofitting improved the loading capacity of boiler when high pressure heaters are separated and coal mills are stopped.The hidden troubles of heating surface corrosion were be reduced.The boilers' safety and economy is enhanced.