Effect of louver opening degree on anti-freezing performance of natural drafted air-cooling tower
|更新时间:2025-09-28
|
Effect of louver opening degree on anti-freezing performance of natural drafted air-cooling tower
Thermal Power GenerationVol. 45, Issue 4, Pages: 70-75(2016)
作者机构:
西安交通大学动力工程多相流国家重点实验室
作者简介:
基金信息:
DOI:
CLC:TM62
Published:2016
稿件说明:
移动端阅览
GU Hongfan, WANG Haijun, CHEN Qi, et al. Effect of louver opening degree on anti-freezing performance of natural drafted air-cooling tower[J]. Thermal power generation, 2016, 45(4): 70-75.
DOI:
GU Hongfan, WANG Haijun, CHEN Qi, et al. Effect of louver opening degree on anti-freezing performance of natural drafted air-cooling tower[J]. Thermal power generation, 2016, 45(4): 70-75.DOI:
Effect of louver opening degree on anti-freezing performance of natural drafted air-cooling tower
at extremely low ambient temperatures and with low heat flux operation conditions
the water temperature can reach freezing point near the end of the tubes
resulting in deformation and cracking of the heat transfer tubes
which affects the safety operation of the unit.Thus
taking the vertical indirect air-cooling tower in 2×350MW units as the example
this paper numerically simulate the heat transfer performance of the towers at low temperatures in winter
by computational fluid dynamics(CFD)method.Through adjusting the opening degree of the louvers
different flow fields and temperature fields inside the indirect air-cooling tower can be obtained.Then
the influence of louvers opening degree on cooling capacity of the air cooling tower is investigated.The results show that
the air-cooling system can avoid freezing phenomenon by regulating the opening degree of the louvers into a proper value when the wind leakage rate of the closed louver is below the limit value.However
only reducing opening degree of the louvers at windward and leeward side will aggravate the harsh operation environments of other sector radiators
causing high risk in heat transfer tube cracking and deformation.Therefore
it is recommended that all the louvers should be adjusted simultaneously during anti-freezing operation at low heat flux condition with extremely low ambient temperature.