A 600 MW unit in Laoz applies octagonal corner tangentially-fired boiler with design coal of low heat value lignite coal.The load increase or decrease rate of this unit is higher than the actual load change rate of the similar 600 MW units in China.Due to such reasons as the low volumetric heat release rate of the boiler
limited grinding ability of the coal mill
large size of coal particles and lack of effective regulation on coal fineness
several problems occurred in this unit
like high stable load without diesel oil support
large amount of carbon content in the bottom slag
poor flame stability
and so on.Thus
combustion adjustment measures like the secondary air flow distribution test and coal mill combination changing were performed
to improve the combustion conditions.The results show the combustible matter content in the bottom slag reduced from 28.28%to 15.10%
in the fly ash dropped from 0.83%to 0.63%
and the unburned carbon heat loss decreased from 2.54% to 1.45%.The mechanical incomplete combustion heat loss reduced