Function analysis for automatic depressurization system in AP1000 nuclear power plant
Taking a large break loss accident of cold leg in primary circuit in AP1000 nuclear power plant as the example
this paper investigated the effects of automatic depressurization system(ADS-1—ADS-4)on pressure in the primary system and containment
and passive core cooling system(PXS)and core water level.The results show that
in the early stage of accident
a large amount of coolant was released from the break
the ADS-1—ADS-3had little effect on reducing the primary system pressure.However
in the late stage
the ADS-4played a role in reducing the primary system pressure.The ADS-1—ADS-3affected the core make-up water tank(CMT)and accumulator(ACC)little.The ADS-4played a key role in actuating in-containment refueling water storage tank(IRWST)gravity injection and preventing reactor core from being uncovered.