Control system design for test platform of key components in 700 ℃ ultra supercritical power units
|更新时间:2025-09-28
|
Control system design for test platform of key components in 700 ℃ ultra supercritical power units
Thermal Power GenerationVol. 45, Issue 9, Pages: 56-60(2016)
作者机构:
中国华能集团清洁能源技术研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TM621;TP273
Published:2016
稿件说明:
移动端阅览
SUN Yangyang, YAO Guopeng, ZHONG Yiqing, et al. Control system design for test platform of key components in 700 ℃ ultra supercritical power units[J]. Thermal power generation, 2016, 45(9): 56-60.
DOI:
SUN Yangyang, YAO Guopeng, ZHONG Yiqing, et al. Control system design for test platform of key components in 700 ℃ ultra supercritical power units[J]. Thermal power generation, 2016, 45(9): 56-60.DOI:
Control system design for test platform of key components in 700 ℃ ultra supercritical power units
摘要
为使我国首个700℃超超临界燃煤发电机组关键部件验证试验平台能够安全、高效、长周期运行
结合日立H5000M DCS特点
设计了该机组关键部件验证试验平台控制系统
通过分析项目组态、调试过程中遇到的问题
完善了控制系统功能设计
建立了有效的控制运行策略。经现场冷态调试及热态调试
该控制系统超调在0.5%以内
响应时间为60s
升温速率为2~3℃/min
控制效果良好。目前
试验平台已通过168h试运行
系统整体运行平稳
控制系统的稳定性和调节性良好
自动投用率达到100%
联锁投入率达到100%。
Abstract
To ensure the safe
efficient and long-term operation of the first test platform for key components in 700 ℃ ultra supercritical power units
the control system for this key components test platform was designed
combining with the characteristics of Hitachi DCS.By analyzing the problems occurred during the process of project configuration and debugging
the system function was improved and the control strategy was established in effect.After the cold state debugging and hot state debugging
the overshoot of this control system is controlled within 0.5%
the response time is 60 s
and the heating rate is 2~3 ℃/min
indicating the temperature control effect at the superheater specimen outlet is good.At present
this test platform has successfully taken the 168 hcommissioning
and the whole system runs stably
the stability and adjustability of the control system is good
the automatic commissioning rate can reach up to 100%
and the interlocking operation rate can reach up to 100%.