Coordinated control and optimization for unit equipped with single-line auxiliaries during low load operation
|更新时间:2025-09-28
|
Coordinated control and optimization for unit equipped with single-line auxiliaries during low load operation
Thermal Power GenerationVol. 45, Issue 11, Pages: 120-124(2016)
作者机构:
1. 西安热工研究院有限公司
2. 华能洛阳发电有限责任公司
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2016
稿件说明:
移动端阅览
CHEN Zhigang, LIU Baicheng, WANG Tian, et al. Coordinated control and optimization for unit equipped with single-line auxiliaries during low load operation[J]. Thermal power generation, 2016, 45(11): 120-124.
DOI:
CHEN Zhigang, LIU Baicheng, WANG Tian, et al. Coordinated control and optimization for unit equipped with single-line auxiliaries during low load operation[J]. Thermal power generation, 2016, 45(11): 120-124.DOI:
Coordinated control and optimization for unit equipped with single-line auxiliaries during low load operation
A supercritical coal-fired power generating unit equipped with single-line auxiliaries ran at 50%load for a long time after being put into service
the poor control accuracy at low load makes the unit be unable to satisfy the requirements of coordination control
and brings out several problems
such as the superheat temperature
large fluctuation of feedwater and main steam pressures
great disturbance of the induced draft fan
slow load response to the primary frequency regulation
unable to effectively guarantee the unit thermal efficiency and safety risk.To solve these problems
this paper puts forward a series of countermeasures
like modifying the mill inlet air flow measurement device
improving the furnace pressure control
reducing the primary air ratio during low load operation
dynamically adapting the feedwater and superheating temperature control strategy using variable parameter
adding the primary frequency regulation valve position response demand
and optimizing the boiler main control circuit and low load feed-forward loop.The low load 170~200MW(48%~57%)varying load test results indicate that
the optimized coordination control can meet the unit's operation requirement during load increasing/descending process.This optimized control strategy has a certain reference for low load safe operation of units equipped with single line auxiliaries.