Experimental research on simultaneous removal of SO3 by low-low temperature economizer in units firing high-sulfur coal
|更新时间:2025-09-28
|
Experimental research on simultaneous removal of SO3 by low-low temperature economizer in units firing high-sulfur coal
Thermal Power GenerationVol. 45, Issue 12, Pages: 30-36(2016)
作者机构:
西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:X773;TM621.2
Published:2016
稿件说明:
移动端阅览
LU Jun, LIU Yongqiang, ZHOU Fei, et al. Experimental research on simultaneous removal of SO3 by low-low temperature economizer in units firing high-sulfur coal[J]. Thermal power generation, 2016, 45(12): 30-36.
DOI:
LU Jun, LIU Yongqiang, ZHOU Fei, et al. Experimental research on simultaneous removal of SO3 by low-low temperature economizer in units firing high-sulfur coal[J]. Thermal power generation, 2016, 45(12): 30-36.DOI:
Experimental research on simultaneous removal of SO3 by low-low temperature economizer in units firing high-sulfur coal
There are some problems during application of low-low temperature economizer in coal-fired units
especially the safety problem in units firing high-sulfur coal.Thus
an experimental platform of lowlow temperature economizer for high-sulfur coal units was built and used to investigate the simultaneous removal of SO_3 from flue gas.The experimental results are as follows.For different kinds of coal
the conversion ratio of SO_2 to SO_3in flue gas were about the same
which was 1.5%.When the temperature of flue gas at the end of the test section of the self-built low-low economizer was below the acid dew point
the simultaneous removal ratio of SO_3 were from 70.9%to 91.9%
indicating the removal effect was dramatic.When the concentration of fly ash in flue gas was high enough
the simultaneous removal ratio of SO_3 increased as the ratio of ash to sulfur decreased
and when the ratio of ash to sulfur were above 150
the simultaneous removal ratio of SO_3 were tending to be stable.Meanwhile
when the outlet temperature of flue gas was below the acid dew point
the outlet temperature had no significant effect on the simultaneous removal ratio of SO_3.Through the application of SO_3 flue gas conditioning
the order magnitude of the fly ash resistivity at the outlet of the test section decreased to 1.08×10~9 to 5.1×1 0~(10) Ω·cm
which was at the high efficient ash removal range and would benefit the efficient removal of the fly ash.