Optimization of control strategy for water coal ratio in ultra-supercritical units
|更新时间:2025-09-28
|
Optimization of control strategy for water coal ratio in ultra-supercritical units
Thermal Power GenerationVol. 46, Issue 4, Pages: 115-119(2017)
作者机构:
深能合和电力(河源)有限公司
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2017
稿件说明:
移动端阅览
GU Dedong, LI Enpeng. Optimization of control strategy for water coal ratio in ultra-supercritical units[J]. Thermal power generation, 2017, 46(4): 115-119.
DOI:
GU Dedong, LI Enpeng. Optimization of control strategy for water coal ratio in ultra-supercritical units[J]. Thermal power generation, 2017, 46(4): 115-119.DOI:
Optimization of control strategy for water coal ratio in ultra-supercritical units
摘要
某厂2×600 MW超超临界机组水冷壁超温严重
施行低氮燃烧器改造后
主蒸汽、再热蒸汽温度波动较大
为此
将水煤比控制策略由原来煤跟水控制修改为水跟煤控制
并在此基础上进行了机组协调控制策略的优化
变负荷过程中采用变参数控制
将动态、稳态控制策略分离
升、降负荷控制参数独立设置。优化后机组水冷壁超温大幅减少
主蒸汽、再热蒸汽温度控制品质提高
主蒸汽压力变化平稳
可为同类型机组控制策略优化提供参考依据。
Abstract
The overheat of water walls is serious in ultra-supercritical 2 × 600 MW unit boilers in a power plants. After low NOx burner transformation
the fluctuation of main steam and reheat steam temperature became large. To solve this problem
the original water coal ratio control strategy(coal following water) was modified(the new logic is water following coal). On this basis
optimization on control strategy of the unit coordinated control system was carried out. Variable parameters were set in variable load process
the dynamic and steady state control strategy was separated
and the load rise/descend control parameters were set independently. After the optimization
the overheat of the boiler water walls was drastically reduced
the main steam and reheat steam temperature control quality was improved
and the main steam pressure changed smoothly
which can provide references for the optimization of control strategies for the same type units.