Analysis and optimization for online operation performance indexes of the ultra supercritical 1 000 MW double-reheat unit in Laiwu Power Plant
|更新时间:2025-09-28
|
Analysis and optimization for online operation performance indexes of the ultra supercritical 1 000 MW double-reheat unit in Laiwu Power Plant
Thermal Power GenerationVol. 46, Issue 12, Pages: 133-136(2017)
作者机构:
1. 西安热工研究院有限公司
2. 华能莱芜发电有限公司
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2017
稿件说明:
移动端阅览
WU Tao, CHU Mo, MA Pengbo, et al. Analysis and optimization for online operation performance indexes of the ultra supercritical 1 000 MW double-reheat unit in Laiwu Power Plant[J]. Thermal power generation, 2017, 46(12): 133-136.
DOI:
WU Tao, CHU Mo, MA Pengbo, et al. Analysis and optimization for online operation performance indexes of the ultra supercritical 1 000 MW double-reheat unit in Laiwu Power Plant[J]. Thermal power generation, 2017, 46(12): 133-136.DOI:
Analysis and optimization for online operation performance indexes of the ultra supercritical 1 000 MW double-reheat unit in Laiwu Power Plant
摘要
基于华能莱芜发电有限公司超超临界1 000 MW二次再热机组的优化系统平台
通过对实时计算的性能指标进行历史数据统计分析
得到与机组性能指标相关联的主要指标
即锅炉效率、汽轮机热耗率与发电机功率的关系曲线
从而了解机组的运行水平
并与性能考核试验结果进行对比
发现计算结果具有较高的匹配性;采用工况寻优模块得到机组最佳的性能运行曲线
对相同负荷下不同运行工况数据进行对比分析。结果表明:通过常规的运行调整可进一步挖掘机组节能潜力
预计可进一步节约煤耗3.99~4.59 g/(k W·h)
这对二次再热机组优化运行具有重要的指导意义。
Abstract
Based on the optimization system platform for the ultra supercritical 1000 MW double reheat unit in China Huaneng Laiwu Power Generation Co.
Ltd.
statistical analysis for historical data of the performance index of real-time computation was carried out to obtain the relationship curves between the generator output and the main performance indexes of the unit
such as the boiler efficiency and steam turbine heat rate.Thus
the operation level of the unit was obtained and compared with the unit performance evaluation results
it finds that the calculation result agrees well with the test result.Moreover
the optimal performance curve of the unit was obtained by using the condition optimization module
and the data under different operating conditions at the same load were compared.The results show that
the energy saving potential can be further explored by routine operation adjustment
and the coal consumption of 3.99~4.59 g/(kW·h) can be further saved
which has important guiding significance for optimal operation of the double reheat units.