Non-destructive Detection of XLPE Cable Insulation Based on the Method of Polarization-depolarization Current
|更新时间:2025-12-08
|
Non-destructive Detection of XLPE Cable Insulation Based on the Method of Polarization-depolarization Current
Vol. 41, Issue 8, Pages: 2643-2649(2015)
作者机构:
四川大学电气信息学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2015,
Published:2015
稿件说明:
移动端阅览
LEI Yong, JIANG Shichao, ZHOU Kai, et al. Non-destructive Detection of XLPE Cable Insulation Based on the Method of Polarization-depolarization Current[J]. 2015, 41(8): 2643-2649.
DOI:
LEI Yong, JIANG Shichao, ZHOU Kai, et al. Non-destructive Detection of XLPE Cable Insulation Based on the Method of Polarization-depolarization Current[J]. 2015, 41(8): 2643-2649.DOI:
Non-destructive Detection of XLPE Cable Insulation Based on the Method of Polarization-depolarization Current
In order to accurately assess the insulation of cross-linked polyethylene(XLPE) cables in power distribution networks
we researched non-destructive detection devices and relevant assessment methods based on the characteristic parameters of polarization-depolarization current(PDC). Taking new and aged cables with different lengths for examples
we analyzed and compared their insulation using the PDC method. By comparing the depolarization discharge current curves of cables
it is found the current level plunges from μA to n A at the beginning of the discharge
meanwhile
the aged cables discharge faster than their newer counterparts. Then after a certain while
the current level falls from n A to p A and eventually stabilizes at p A level
at this time the depolarization current of aged cables is much larger than that of the new cables. Depolarization current increases with the charging voltage and the charging time. In the end
through non-linear fitting of the experimental data
we can obtain the relationship between the fitted curves and the dielectric constant and conductivity of the cable insulation layer. The results verify the accuracy and reliability of the PDC method in assessing XLPE cable insulation.