Selection Criteria of High-voltage Submarine Cables for Offshore Wind Farms by Life Cycle Cost
|更新时间:2025-12-08
|
Selection Criteria of High-voltage Submarine Cables for Offshore Wind Farms by Life Cycle Cost
Vol. 41, Issue 8, Pages: 2674-2680(2015)
作者机构:
1. 华南理工大学电力学院
2. 中国能源建设集团广东省电力设计研究院
3. 广东工业大学轻工化工学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2015,
Published:2015
稿件说明:
移动端阅览
LIU Gang, CAO Jingying, LU Ying, et al. Selection Criteria of High-voltage Submarine Cables for Offshore Wind Farms by Life Cycle Cost[J]. 2015, 41(8): 2674-2680.
DOI:
LIU Gang, CAO Jingying, LU Ying, et al. Selection Criteria of High-voltage Submarine Cables for Offshore Wind Farms by Life Cycle Cost[J]. 2015, 41(8): 2674-2680.DOI:
Selection Criteria of High-voltage Submarine Cables for Offshore Wind Farms by Life Cycle Cost
高电压等级故障损失成本至少比低电压等级海缆方案高出8.8×103万元;2回110 k V 3×500 mm2高压XLPE绝缘钢丝铠装海缆方案LCC等额年值(3.08×103万元/a)最小
该方案最优。
Abstract
In order to develop a criterion for high-voltage submarine cable selection in offshore wind farms that take the characteristics of submarine cable’s life-cycle into consideration
we created a life cycle cost(LCC) model of high-voltage submarine cable under the constraint that the capacity of submarine cable transmission is greater than that of designed wind power output. The model includes the costs of input
laying
electricity loss
failure
maintenance
and recycling net investment. Then the selection criterion is to achieve the minimum equivalent uniform annual worth of LCC. Case study of a Chinese offshore wind farm submarine cable selection is proposed. The results show that
the costs of input
electricity loss and failure comprise the largest portions of LCC
which are up to 26.4%
30.8% and 62.0%
respectively
and the maximum front-end investment is less than 40% of the LCC. At the same voltage level
the electricity loss for a single core cable plan is 4.68×107 RMB more than that for a three-core cable plan at least. With the same core number
the cost of failure in a high-voltage submarine cable plan is 8.8×107 RMB more than that of a low-voltage plan at least. The optimal plan is to have two circuits of 110 k V 3×500 mm2 high-voltage XLPE insulation steel-wire-armored submarine cable
since its equivalent uniform annual worth of LCC(3.08×107 RMB/a) is the smallest.