Application of Signals Separated Band Energy Spectrum and Mahalanobis Clustering Algorithm for Switchgear Partial Discharge Pattern Recognition
|更新时间:2025-12-08
|
Application of Signals Separated Band Energy Spectrum and Mahalanobis Clustering Algorithm for Switchgear Partial Discharge Pattern Recognition
Vol. 41, Issue 10, Pages: 3332-3341(2015)
作者机构:
1. 重庆大学输配电装备及系统安全与新技术国家重点实验室
2. 2. 国网重庆市电力公司江北供电分公司
3. 南方电网中山市供电公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 October 2015,
Published:2015
稿件说明:
移动端阅览
CHEN Pan, YAO Chenguo, LIAO Ruijin, et al. Application of Signals Separated Band Energy Spectrum and Mahalanobis Clustering Algorithm for Switchgear Partial Discharge Pattern Recognition[J]. 2015, 41(10): 3332-3341.
DOI:
CHEN Pan, YAO Chenguo, LIAO Ruijin, et al. Application of Signals Separated Band Energy Spectrum and Mahalanobis Clustering Algorithm for Switchgear Partial Discharge Pattern Recognition[J]. 2015, 41(10): 3332-3341.DOI:
Application of Signals Separated Band Energy Spectrum and Mahalanobis Clustering Algorithm for Switchgear Partial Discharge Pattern Recognition
In order to overcome defects of traditional ultra high frequency(UHF) detection such as high cost
strict requirements on system sampling rate and data storage
we developed an economical UHF on-line monitoring system for HV switchgear by incorporating down-mixing with power detection technology. We used the proposed system to monitor the partial discharge(PD) signals of four typical defect models
namely surface discharge
air gap discharge
needle-plate discharge and free particle discharge
and obtained their energy spectrum in different frequency bands. Then
taking the sub-band energy of PD signals as eigenvectors
we proposed a PD pattern recognition method for HV switchgear by using Mahalanobis distance as clustering analysis tool.The results show that
the energy distributions of different PD models are more significantly different than the same PD models
and that different types of PD apparently present a feature of regional clustering in energy triangle plot. Moreover
by using the proposed PD recognition method
the accurate rate of PD recognition for the four typical PD defects is 99.125%.