Influence of Wind Speed and Dust Particle Size on Corona Inception Voltage of DC Fittings
|更新时间:2025-12-08
|
Influence of Wind Speed and Dust Particle Size on Corona Inception Voltage of DC Fittings
Vol. 42, Issue 6, Pages: 1855-1861(2016)
作者机构:
1. 西安交通大学电气工程学院
2. 中国电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2016,
Published:2016
稿件说明:
移动端阅览
HE Bo, MAO Yan, ZHAO Heng, et al. Influence of Wind Speed and Dust Particle Size on Corona Inception Voltage of DC Fittings[J]. 2016, 42(6): 1855-1861.
DOI:
HE Bo, MAO Yan, ZHAO Heng, et al. Influence of Wind Speed and Dust Particle Size on Corona Inception Voltage of DC Fittings[J]. 2016, 42(6): 1855-1861.DOI:
Influence of Wind Speed and Dust Particle Size on Corona Inception Voltage of DC Fittings
It is necessary to study the effects of wind speed and dust particle size on DC corona inception voltage of fittings so as to design and maintain HVDC transmission lines under extreme climate conditions. Therefore
four different-sized aluminum grading rings were taken as research objects. The corona inception voltage of each of these grading rings was tested under three experimental conditions: still air
10
2
5 m/s wind speed with dust particles
and the diameter of particle is under 65 μm and 105 μm
respectively. The results were then verified by ANSYS simulation. It is indicated that the corona inception voltage will decreases under the influences of wind and dust particles. Moreover
the voltage under the same dust-particle concentration increases along with the wind speed raising. The voltage under 65-μm diameter dust particle
s is lower than that under 105-μm ones at each wind speed.