Rapid Testing Method of Low Frequency Dielectric Response Based on Multiple Frequency Excitation
|更新时间:2025-12-08
|
Rapid Testing Method of Low Frequency Dielectric Response Based on Multiple Frequency Excitation
Vol. 42, Issue 11, Pages: 3548-3553(2016)
作者机构:
1. 西南交通大学电气工程学院
2. 云南电网有限责任公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:20 November 2016,
Published:2016
稿件说明:
移动端阅览
ZHOU Lijun, YE Guo, LIU Dongcai, et al. Rapid Testing Method of Low Frequency Dielectric Response Based on Multiple Frequency Excitation[J]. 2016, 42(11): 3548-3553.
DOI:
ZHOU Lijun, YE Guo, LIU Dongcai, et al. Rapid Testing Method of Low Frequency Dielectric Response Based on Multiple Frequency Excitation[J]. 2016, 42(11): 3548-3553.DOI:
Rapid Testing Method of Low Frequency Dielectric Response Based on Multiple Frequency Excitation
摘要
频域介电频谱(FDS)测试是用于诊断变压器绝缘状态的有效方法之一
由于采用扫频方式测试
低频阶段所需要耗费的测试时间长
对于某些测试时间特别有限的工况不一定适用。为尽可能减少测量时间
研究了采用混频激励测试FDS的方法
其主要思想是使用多个频率正弦电压叠加的信号作为激励源
将采集到的电流曲线分解为激励信号对应频率下的多个正弦波形
分别计算获得复电容;并以油隙为试验对象
比对混合频率和单个频率电压作用下的电流波形
验证了混频激励FDS测试原理的正确性;同时以油纸绝缘试样和实体变压器为试验对象
与传统FDS(使用IDAX300型介电响应测试仪)测试结果比对
结果表明:各频率下两者测试的复电容值都基本一致
但前者的测试时间可大幅缩短。
Abstract
Frequency domain dielectric spectroscopy(FDS)
a diagnostic method to diagnose the insulation condition of transformers
needs to scan the excitation frequency point-by-point in the general condition
which takes a long period in the low frequency. So it may not be appropriate in some time-limited conditions. To solve this issue
we put forward a testing method of FDS affected by hybrid frequency voltage. The proposed method imposes a composite hybrid-frequency signal to the dielectric as input stimulus. The current response information is decomposed into several sinusoidal waves which match the corresponding frequency
then the complex capacitance can be acquired through calculation. The oil clearance experimental results reveal that a contrast of the decomposition value of the hybrid frequency response and the value of single frequency response between the two methods shows the correctness of the proposed FDS. Meanwhile
this method is adopted to measure the dielectric spectrum of oil-paper insulation and real transformer and compared with the scanning frequency results of IDAX300. The results show that the proposed method almost coincides with the conventional FDS method in complex capacitance
while the proposed method can remarkably save time.