Correlation Character Between Switch Gear’s Partial Discharge Quantity and Air Decomposition Components Under Needle-plate Defect Model
|更新时间:2025-12-08
|
Correlation Character Between Switch Gear’s Partial Discharge Quantity and Air Decomposition Components Under Needle-plate Defect Model
Vol. 42, Issue 12, Pages: 3948-3954(2016)
作者机构:
1. 重庆大学输配电装备及系统安全与新技术国家重点实验室
2. 海南电力技术研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 December 2016,
Published:2016
稿件说明:
移动端阅览
ZHANG Xiaoxing, ZHOU Lei, QIU Yinjun, et al. Correlation Character Between Switch Gear’s Partial Discharge Quantity and Air Decomposition Components Under Needle-plate Defect Model[J]. 2016, 42(12): 3948-3954.
DOI:
ZHANG Xiaoxing, ZHOU Lei, QIU Yinjun, et al. Correlation Character Between Switch Gear’s Partial Discharge Quantity and Air Decomposition Components Under Needle-plate Defect Model[J]. 2016, 42(12): 3948-3954.DOI:
Correlation Character Between Switch Gear’s Partial Discharge Quantity and Air Decomposition Components Under Needle-plate Defect Model
Air switch gear plays an important role in the distribution network. Therefore
in view of the partial discharge monitoring of switch gear
we put forward a method of monitoring by testing the air decomposition components. In the self-built air partial discharge test platform
air was decomposed to form characteristic gas by PD in needle-plate model
the voltage on the needle-plate was adjusted to control the degree of PD
and the smoke analysis instrument and the discharge pulse current method were adopted to explore the correlation characteristics between partial discharge quantity and air decomposition components. Analyses of experimental data show that air can be decomposed in PD discharge needle-plate defects
generating
characteristic CO and NO
2
gas
the gas volume concentration increases as the discharge time increasing
and the early stage of the discharge gas volume concentration such as discharge presents the linear growth trend.The reaction matter decreases in discharge and presents a saturation phenomenon
and the degree of saturation of NO
2
is below that of CO. Because the gas concentration of CO and NO
2
gas rate trends to saturate
the dischage presents a linear relationship of saturation.