Simulation Research on Control Method Based on Parallel Railway Static Power Conditioner of Electrified Railway
|更新时间:2025-12-08
|
Simulation Research on Control Method Based on Parallel Railway Static Power Conditioner of Electrified Railway
Vol. 42, Issue 11, Pages: 3533-3538(2016)
作者机构:
1. 兰州交通大学自动化与电气工程学院
2. 应用材料(西安)有限公司
3. 国网宁夏电力公司培训中心
作者简介:
基金信息:
DOI:
CLC:
Published Online:20 November 2016,
Published:2016
稿件说明:
移动端阅览
TIAN Mingxing, ZHANG Junqiang, DONG Xiaodong, et al. Simulation Research on Control Method Based on Parallel Railway Static Power Conditioner of Electrified Railway[J]. 2016, 42(11): 3533-3538.
DOI:
TIAN Mingxing, ZHANG Junqiang, DONG Xiaodong, et al. Simulation Research on Control Method Based on Parallel Railway Static Power Conditioner of Electrified Railway[J]. 2016, 42(11): 3533-3538.DOI:
Simulation Research on Control Method Based on Parallel Railway Static Power Conditioner of Electrified Railway
and negative sequence in the three-phase line side of the electrified railway traction power supply system
and to meet the needs of heavy compensation capacity of the electrified railway
a comprehensive compensation scheme
which was formed by the railway static power condition(RPC) and the step-down transformer
was proposed
and the control method of the parallel RPC was specifically researched. The balanced compensation current detection method was used in instruction current detecting and triangle wave comparison of proportion resonance(PR) controller was used in compensation current controlling. Also
the carrier phase shift(CPS) technology was applied in RPC controlling. At last
the modeling and simulation of the compensation scheme which was composed of two parallel RPC were built on the MATLAB/Simulink. The simulation results show that the three-phase line side currents will keep balanceable after one fundamental frequency cycle when RPC has been put in operation. By adopting the CPS technology further
the three-phase line side currents total harmonic distortion rate is reduced from 8.04% to 2.24%. The research work here confirms the feasibility and superiority of the parallel RPC for solving the power quality problems in the three-phase line side of the traction power supply system
and also provides a valuable reference for the engineering application of the parallel RPC.