Winding Impulse Voltage Distribution Based on Transformer Reduced-scale Model
|更新时间:2025-12-08
|
Winding Impulse Voltage Distribution Based on Transformer Reduced-scale Model
Vol. 42, Issue 12, Pages: 3955-3963(2016)
作者机构:
1. 重庆大学输配电装备及系统安全与新技术国家重点实验室
2. 云南电网有限责任公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 December 2016,
Published:2016
稿件说明:
移动端阅览
YANG Qing, CHEN Yong, SIMA Wenxia, et al. Winding Impulse Voltage Distribution Based on Transformer Reduced-scale Model[J]. 2016, 42(12): 3955-3963.
DOI:
YANG Qing, CHEN Yong, SIMA Wenxia, et al. Winding Impulse Voltage Distribution Based on Transformer Reduced-scale Model[J]. 2016, 42(12): 3955-3963.DOI:
Winding Impulse Voltage Distribution Based on Transformer Reduced-scale Model
The impulse potential distribution in actual power transformer winding(due to possessing no tap pin)can not directly be measured. Using similar electric property and tapped transformer model instead of the original model to research the measuring impulse voltage distribution has important engineering practical value. To research all kinds of physical constants and electric field intensity under the same conditions between reduced-scaled and original models
according to the relationship between physical quantities
we established a simplified shrinkage ratio criterion. Secondly
according to the actual power transformer original model and shrinkage ratio criterion
we designed a similar ratio 1/20
typed 10 k VA-220 V/2 400 V tapped transformer reduced-scaled model. Then
using the finite element simulation software COMSOL Multiphysics
we simulated the reduced-scaled and original models of the electric field
magnetic field
and electromagnetic field. Finally
we established a test platform to measure the winding impulse voltage distribution of transformer reduced-scaled model under ns pulse voltage. The comprehensive and comparative analyses of the simulation verify the correctness of the rule of shrinkage ratio. It is found that the impulse voltage distribution of transformer winding is uneven and high-voltage side withstanding voltage is higher.