DC Bias Analysis and Suppression of Transformers in Henan Power Grid After Tianshan-Zhongzhou UHVDC Transmission Project Commissioning
|更新时间:2025-12-08
|
DC Bias Analysis and Suppression of Transformers in Henan Power Grid After Tianshan-Zhongzhou UHVDC Transmission Project Commissioning
Vol. 43, Issue 2, Pages: 611-618(2017)
作者机构:
1. 国网河南省电力公司电力科学研究院国网输电线路舞动防治技术重点实验室
2. 黄河勘测规划设计有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 February 2017,
Published:2017
稿件说明:
移动端阅览
DONG Manling, YAO Shuai, GUO Lei, et al. DC Bias Analysis and Suppression of Transformers in Henan Power Grid After Tianshan-Zhongzhou UHVDC Transmission Project Commissioning[J]. 2017, 43(2): 611-618.
DOI:
DONG Manling, YAO Shuai, GUO Lei, et al. DC Bias Analysis and Suppression of Transformers in Henan Power Grid After Tianshan-Zhongzhou UHVDC Transmission Project Commissioning[J]. 2017, 43(2): 611-618.DOI:
DC Bias Analysis and Suppression of Transformers in Henan Power Grid After Tianshan-Zhongzhou UHVDC Transmission Project Commissioning
A large DC earth current will have a negative impact on Henan power grid
when ±800 kV Tianshan-Zhongzhou(Tianzhong) UHVDC transmission project operates in ground-return mode or asymmetric operation mode. Therefore
based on the practical operation of Henan power grid
a simulation model to analyze the DC bias was established. According to the measured results on site
the DC bias classification protection of Henan power grid was made. The capacitive-type DC suppression device with reliable return system was developed and operated in Henan power grid. The results show that the magnitude of the DC bias current is mainly affected by the surface potential rising distribution
also affected by the distance between the substations and the number of outlets. Special attention should be paid to the DC bias of the station which is far away from other station and have less outlets. The principle of classified protection is that the station of which DC bias exceeds the standard needs to be suppressed
and substation with significant DC bias needs to be further monitored. The capacitive-type DC suppression device which has a bypass protection will reliably operate when the control system is de-energized. When this capacitive-type DC suppression device is adopted in the 220 kV Minghe substation
the DC bias is effectively suppressed
and the safe and reliable operation of Henan power grid is ensured. Therefore
the influence of DC bias to the transformer of Henan power grid can be effectively solved after Tianzhong UHVDC transmission project commissioning.