Evaluation Method for Thermal State of Extra-high Voltage XLPE Power Cable Termination
|更新时间:2025-12-08
|
Evaluation Method for Thermal State of Extra-high Voltage XLPE Power Cable Termination
Vol. 43, Issue 2, Pages: 682-688(2017)
作者机构:
中国电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 February 2017,
Published:2017
稿件说明:
移动端阅览
LIANG Zhengbo, XU Mingzhong, HOU Junping, et al. Evaluation Method for Thermal State of Extra-high Voltage XLPE Power Cable Termination[J]. 2017, 43(2): 682-688.
DOI:
LIANG Zhengbo, XU Mingzhong, HOU Junping, et al. Evaluation Method for Thermal State of Extra-high Voltage XLPE Power Cable Termination[J]. 2017, 43(2): 682-688.DOI:
Evaluation Method for Thermal State of Extra-high Voltage XLPE Power Cable Termination
The insulation fault of extra-high voltage(EHV) cross-linking polyethylene(XLPE) power cable termination has a great influence on stability of power grid
and it is very important to effectively evaluate the thermal state of EHV XLPE power cable termination for forecasting insulation fault. In order to study the evaluation method for thermal state of EHV XLPE power cable termination
we analyzed thermal distribution characteristic of EHV XLPE power cable termination surface
put forward a thermal state evaluation method on the basis of the maximum temperature difference of EHV XLPE power cable termination surface. According to the requirements of IEC 62067: 2011 and GB/T 22078—2008
we designed and performed a prequalification test of 500 kV XLPE cable system
and analyzed the thermal distribution characteristic of the EHV XLPE power cable termination surface at different ambient temperatures by method of thermal infrared imaging. The results show that environmental interference of thermal field analysis can be effectively reduced by evaluation for the maximum temperature difference of EHV XLPE power cable termination surface. If the maximum temperature difference Δθ≈1 ℃
EHV XLPE power cable termination is in good thermal state
and if the maximum temperature difference Δθ 1 ℃
EHV XLPE power cable termination is in bad thermal state. If Δθ is too large
it is suggested that EHV XLPE cable termination has an abnormal thermal state. The availability of the thermal state evaluation method for EHV XLPE power cable termination is verified by experiments.