Vector Location Method for Field Strength of Power Transmission Lines
|更新时间:2025-12-08
|
Vector Location Method for Field Strength of Power Transmission Lines
Vol. 43, Issue 3, Pages: 1006-1013(2017)
作者机构:
武汉大学电气工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 March 2017,
Published:2017
稿件说明:
移动端阅览
WU Dengguo, LI Xiaoming, LIU Zhensheng, et al. Vector Location Method for Field Strength of Power Transmission Lines[J]. 2017, 43(3): 1006-1013.
DOI:
WU Dengguo, LI Xiaoming, LIU Zhensheng, et al. Vector Location Method for Field Strength of Power Transmission Lines[J]. 2017, 43(3): 1006-1013.DOI:
Vector Location Method for Field Strength of Power Transmission Lines
摘要
为了对输电线路带电作业的安全距离进行更准确的判定
提出了场强矢量定位方法。建立输电线路周围空间的场强计算模型
根据场强测量点处的场强矢量分量和合成场强最大值、场强传感器的测量误差
寻找测量位置的场强可能接近点坐标集
并根据数学聚类方法将坐标集划分为不同的点群。根据场强测量点的移动特征
确定一个真实接近点群中心实现准确的跟踪定位。最后通过220 k V输电线路二维场强的仿真算例分析
显示82.7%场强测量点的距离误差≤0.1 m
仅有2.75%的≥0.5 m
根据测量点的移动特征可使距离误差基本均减小至0.1 m以下。实际测试中
95%次的测试距离误差≤0.56 m
5%次的测试误差≤1.0 m
基本满足输电线路对于安全距离的测距要求。仿真和测试结果表明了所提方法的有效性
并指出需要进一步研究的方向。
Abstract
To reach more accurate judgement of live working security distance on transmission line
we put forward a method of the field strength vector location.First
we established a calculation model of the electric field around the transmission line.Next
according to the maximum field strength of vector direction and vectors composition at the field measurement dot
and the practical measuring error factors
we searched for the set of possible field strength approach point coordinates.Then
these possible approach points are divided into different point groups according to mathematical clustering method.With the continuous movement feature of the field measurement dot
the center of true approach dot group is determined in order to realize precise tracking and location.Finally
through simulation analysis of two dimensional field strength instance about 220 k V transmission lines.It is showed that the distance error of 82.7% field measurement dots is less than or equal to 0.1 m
and only 2.75% greater than or equal to 0.5 m.Basically
the error is further reduced to less than 0.1 m
according to the continuous movement feature of the field measurement dot.In the practical test
95% test distance error is less than or equal to 0.56 m
and 5% less than or equal to 1.0 m
basically meeting the requirements of the transmission line for safe distance.The simulation and practical test result shows its effectiveness