Influence of Surface Charge on Flashover Voltage of Gas Insulated Substation Basin Insulator Under AC and DC Voltage
|更新时间:2025-12-08
|
Influence of Surface Charge on Flashover Voltage of Gas Insulated Substation Basin Insulator Under AC and DC Voltage
Vol. 43, Issue 3, Pages: 915-922(2017)
作者机构:
1. 华北电力大学新能源电力系统国家重点实验室
2. 华北电力大学高电压与电磁兼容北京市重点实验室
3. 南方电网科学技术研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 March 2017,
Published:2017
稿件说明:
移动端阅览
QI Bo, GAO Chunjia, ZHAO Linjie, et al. Influence of Surface Charge on Flashover Voltage of Gas Insulated Substation Basin Insulator Under AC and DC Voltage[J]. 2017, 43(3): 915-922.
DOI:
QI Bo, GAO Chunjia, ZHAO Linjie, et al. Influence of Surface Charge on Flashover Voltage of Gas Insulated Substation Basin Insulator Under AC and DC Voltage[J]. 2017, 43(3): 915-922.DOI:
Influence of Surface Charge on Flashover Voltage of Gas Insulated Substation Basin Insulator Under AC and DC Voltage
The accumulated surface charge of the insulators in gas insulated substation(GIS) can not only distort the electric field but also decrease the surface flashover voltage.We established a set of high-precision surface charge measurement system utilizing the static capacitive probe method and a matched three-dimensional manipulation devices based on actual 252 k V GIS basin insulator.Referring to the insulating design and flashover properties of GIS basin insulator
an effective surface flashover experimental model was set up.The experimental results indicate that no matter under AC or DC voltage
the more the accumulated surface charge is
and the more the decrease of surface flashover voltage will be.Compared to the surface flashover voltage of insulator under 50 k V AC voltage for 1 hour
the voltage under the condition of 53 k V AC voltage for 3 hours can decrease by 10.2%
while it reaches 23.0% under DC voltage
which indicates the accumulated surface charge has a significant influence on the flashover and must be considered seriously for the insulation design.The research achievement in this paper can provide meaningful reference to the insulating design of insulators in GIS and gas insulated line(GIL).