Influences of Arc Plate on Arc-quenching Performance of Bridge-shape Double-break Circuit Breaker
|更新时间:2025-12-08
|
Influences of Arc Plate on Arc-quenching Performance of Bridge-shape Double-break Circuit Breaker
Vol. 43, Issue 3, Pages: 845-850(2017)
作者机构:
1. 西安理工大学理学院
2. 西安交通大学电力设备电气绝缘国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 March 2017,
Published:2017
稿件说明:
移动端阅览
WANG Qian, QU Jianyu, LI Xingwen. Influences of Arc Plate on Arc-quenching Performance of Bridge-shape Double-break Circuit Breaker[J]. 2017, 43(3): 845-850.
DOI:
WANG Qian, QU Jianyu, LI Xingwen. Influences of Arc Plate on Arc-quenching Performance of Bridge-shape Double-break Circuit Breaker[J]. 2017, 43(3): 845-850.DOI:
Influences of Arc Plate on Arc-quenching Performance of Bridge-shape Double-break Circuit Breaker
a well-designed arc plate can improve the interruption performances.Therefore
we investigate the influences of U-shape arc plate and its position as well as size on the arc-quenching performance.Firstly
a detachable bridge-shape double-break arc quenching chamber with a seizure configuration is designed
and the feasibility of the chamber prototype is invalidated based on the three-dimensional finite element method and multi-dynamic analysis.Then
the influences of three types of arc plates on the interruption performance are investigated via waveforms and key parameters of interruption.The results show that the U-type arc plate can increase the contact repulsion force and lengthen the arc.The effect is enhanced by the enlarged arc plated
and the peak voltage of the arc is increased by 15 V after the add of U-type plate.However
the back-restrike may occur when the U-type arc plate reaches the arc chutes
which is unfavourable for breaking the short current.The research results can provide a reference for the design of circuit breakers.