Insulating Properties of c-C4F8/N2 and c-C4F8/CO2 Mixtures
|更新时间:2025-12-08
|
Insulating Properties of c-C4F8/N2 and c-C4F8/CO2 Mixtures
Vol. 43, Issue 3, Pages: 788-794(2017)
作者机构:
1. 上海交通大学电气工程系
2. 云南电网有限责任公司博士后工作站
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 March 2017,
Published:2017
稿件说明:
移动端阅览
MAN Linkun, DENG Yunkun, XIAO Dengming. Insulating Properties of c-C4F8/N2 and c-C4F8/CO2 Mixtures[J]. 2017, 43(3): 788-794.
DOI:
MAN Linkun, DENG Yunkun, XIAO Dengming. Insulating Properties of c-C4F8/N2 and c-C4F8/CO2 Mixtures[J]. 2017, 43(3): 788-794.DOI:
Insulating Properties of c-C4F8/N2 and c-C4F8/CO2 Mixtures
摘要
为寻找温室效应指数(GWP)低的SF
6
替代气体
研究了c-C
4
F
8
/N
2
与c-C
4
F
8
/CO
2
混合气体的绝缘性能
在球板电极下进行了不同间隙距离、不同气压、不同气体体积分数的c-C
4
F
8
/N
2
与c-C
4
F
8
/CO
2
混合气体工频击穿实验。同时进行了SF
6
、c-C
4
F
8
、N
2
和CO
2
的对比实验
并对击穿之后的分解产物进行了检测。实验结果表明:c-C
4
F
8
/N
2
与c-C
4
F
8
/CO
2
混合气体的击穿电压值都随着间隙距离、气压和c-C
4
F
8
体积分数的增加而增加;c-C
4
F
8
气体与N
2
、CO
2
之间均存在协同效应;稍不均匀场中0.1MPa气压下的c-C
4
F
8
体积分数为30%的c-C
4
F
8
/N
2
与c-C
4
F
8
/CO
2
混合气体的绝缘性能分别约为SF
6
的75%和79%;5%
3
0%体积分数的c-C
4
F
8
/N
2
与c-C
4
F
8
/CO
2
的协同效应系数分别在0.20
0
.79之间和0.15
0
.65之间。从绝缘性能、液化温度和环境保护等方面来看
c-C
4
F
8
/N
2
与c-C
4
F
8
/CO
2
混合气体有可能作为SF
6
的替代气体
应用在电力设备中。
Abstract
To find a friendly alternative gas with low global warming potential(GWP) for SF
6
we investigated insulating properties of c-C
4
F
8
/N
2
and c-C
4
F
8
/CO
2
mixtures.Meanwhile
experiments in a sphere-plate electrode were done in different gap distance
pressures
and gas ratio of c-C
4
F
8
/N
2
and c-C
4
F
8
/CO
2
mixture gas under frequency AC voltage
compared with SF
6
c-C
4
F
8
N
2
and CO
2
in the same conditions.And the decomposition products were detected after breakdown.Experimental results show that the breakdown voltage of mixtures increases as the gas pressure/gap length/ratio of c-C
4
F
8
increases; there is a synergistic effect between c-C
4
F
8
and N
2
/CO
2
; In slightly nonuniform field
insulation performances of 30% c-C
4
F
8
/N
2
and c-C
4
F
8
/CO
2
mixed gas are equal to 75% and 79% of pure SF
6
in 0.1 MPa; the synergistic effect coefficients of c-C
4
F
8
/N
2
and c-C
4
F
8
/CO
2
in 5%
3
0% mixing ratio are between 0.20
0
.79 and 0.15
0
.65
respectively.From the insulating properties
liquefaction temperature standpoint and environment