Calculation Method for Acoustic Power Based on Multivariant Regression Method for AC Transmission Lines
|更新时间:2025-12-08
|
Calculation Method for Acoustic Power Based on Multivariant Regression Method for AC Transmission Lines
Vol. 43, Issue 4, Pages: 1354-1361(2017)
作者机构:
电网环境保护国家重点实验室(中国电力科学研究院)
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 April 2017,
Published:2017
稿件说明:
移动端阅览
WAN Baoquan, WU Xiaorui, PEI Chunming, et al. Calculation Method for Acoustic Power Based on Multivariant Regression Method for AC Transmission Lines[J]. 2017, 43(4): 1354-1361.
DOI:
WAN Baoquan, WU Xiaorui, PEI Chunming, et al. Calculation Method for Acoustic Power Based on Multivariant Regression Method for AC Transmission Lines[J]. 2017, 43(4): 1354-1361.DOI:
Calculation Method for Acoustic Power Based on Multivariant Regression Method for AC Transmission Lines
Due to the different conductor fabrication technologies
test conditions
and climate environment
the empirical formula recommended by Bonneville power administration(BPA) is imprecise when it is used in predicting the audible noise(AN) level of utral-high voltage alternate current(UHVAC) transmission lines in China. Therefore
the audible noise values of seventeen types of bundle conductors whose division numbers are 6
8
9
10 or 12 are measured by using the corona cage
and the calculation method of acoustic power is derived by using a multiple linear regression method. Then
the audible noise levels of two long-term stations(Jiaozuo
Henan Province; Zhongxiang
Hubei Province)
as the 1 000 k V demonstration projects
were calculated by using the BPA formula and the formula presented in this paper. It is shown that the deviation between calculated value by the proposed formula and long-term testing L50 value is 0.66 d B in Henan station
and it is 0.32 d B in Hubei station. Besides
the corresponding deviation by BPA formula is 3.07 d B and 2.14 d B. Therefore
it is demonstrated that the proposed formula is more precise than BPA formula in predicting the AN levels of UHVAC transmission lines. The research results can provide a technical reference for the AN prediction of the UHVAC transmission lines in China.