Study of DC-bias Current Distribution in AC Power System Based on Direct Field-circuit Coupled Model
Vol. 43, Issue 4, Pages: 1333-1340(2017)
作者机构:
1. 武汉大学电气工程学院
2. 国网江苏省电力公司经济技术研究院
3. 国网浙江省电力公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 April 2017,
Published:2017
稿件说明:
移动端阅览
RUAN Jiangjun, XU Wenjie, DING Zhifeng, et al. Study of DC-bias Current Distribution in AC Power System Based on Direct Field-circuit Coupled Model[J]. 2017, 43(4): 1333-1340.
DOI:
RUAN Jiangjun, XU Wenjie, DING Zhifeng, et al. Study of DC-bias Current Distribution in AC Power System Based on Direct Field-circuit Coupled Model[J]. 2017, 43(4): 1333-1340.DOI:
Study of DC-bias Current Distribution in AC Power System Based on Direct Field-circuit Coupled Model
摘要
直流输电系统单极大地方式运行会导致交流系统部分变压器处于直流偏磁状态。基于场路直接耦合方法
建立了±800 k V溪浙和±800 k V灵绍特高压输电工程的直流偏磁计算模型
确定了建模范围和地网参数
并对土壤模型进行了修正
将直流偏磁电流计算值与现场测试结果进行了对比
测试站点的总的相对平均误差≤5%
验证了计算模型的准确性。进一步计算分析了单极大地运行方式下
直流接地极周围110 k V及以上电压等级变电站中变压器的直流偏磁电流分布规律
结果表明:站点的直流电流随着站点与直流接地极之间距离的增加而减小;多台变压器并列运行时
流过每台变压器的直流电流将大幅度下降;首末站点间跨度增大时
流经两站点的电流将增大。研究可为大型交流电网直流电流分布计算和直流偏磁治理提供参考。
Abstract
DC transmission system in monopole-grounded return operation mode may lead to DC magnetic bias of some transformers in AC power system. Based on the direct field-circuit coupled method
the DC magnetic bias calculation models of ±800 k V Xi-Zhe and ±800 k V Ling-Shao UHV transmission project were built. The modeling range and the ground grid parameters were determined
while the soil model was modified as well. The calculated values of DC biasing current were compared with the test results and the total relative average error of each testing station was no more than 5%
verifying the accuracy of the calculation model. The DC biasing current distribution regularities of the substations above 110 k V around the grounding electrode was calculated and analyzed further. The results indicate that the DC current of the substation decreases as the distance between the substation and the grounding electrode increases. When transformers are in parallel operation
the DC current of each transformer decreases greatly. The DC current flowing through the starting and terminal substations will increase with their distance. This research can provide reference to the calculation of DC current distribution in large AC grid and the management of DC magnetic bias.