Improved Droop Control Strategy Based on Line Impedance Identification for Reactive Power Sharing in Microgrid
|更新时间:2025-12-08
|
Improved Droop Control Strategy Based on Line Impedance Identification for Reactive Power Sharing in Microgrid
Vol. 43, Issue 4, Pages: 1271-1279(2017)
作者机构:
1. 天津大学智能电网教育部重点实验室
2. 中华人民共和国科学技术部高技术研究发展中心
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 April 2017,
Published:2017
稿件说明:
移动端阅览
CHEN Xiaoqi, JIA Hongjie, CHEN Shuoyi, et al. Improved Droop Control Strategy Based on Line Impedance Identification for Reactive Power Sharing in Microgrid[J]. 2017, 43(4): 1271-1279.
DOI:
CHEN Xiaoqi, JIA Hongjie, CHEN Shuoyi, et al. Improved Droop Control Strategy Based on Line Impedance Identification for Reactive Power Sharing in Microgrid[J]. 2017, 43(4): 1271-1279.DOI:
Improved Droop Control Strategy Based on Line Impedance Identification for Reactive Power Sharing in Microgrid
the distributed generation(DG) units are operated in the parallel way. In the unequal line impedance condition
the traditional droop control is unable to proportionally share the reactive load. To solve this issue
we proposed an improved droop control strategy based on the line impedance estimator to eliminate the sharing error. Firstly
the relation between the droop control and line impedance was analyzed; secondly
the line impedance estimator of single unit based on the local measurement was built to identify the line impedance with high accuracy. In addition
a voltage compensation term related to the identification result was added to ensure proportional sharing in non-trival impedance condition. Finally
the proposed scheme was applied to a microgrid in MATLAB/Simulink software environment.The simulation results demonstrate the proposed active observer for line impedance is able to identify the line impedance accurately. Based on the estimation result of line impedance
it is able to compensate unmatched voltage drop accurately and make reactive power to share by a reasonable way. The proposed method does not need transmission system to transfer message of DGs
and does not meet the central controller to send synchronizing signal to make sure the synchronism of improved control. The research results prove that the proposed improved droop control strategy is effective.