Breaking and Simulation Method of Arrestors Step-by-step Operating of High Voltage DC Circuit Breaker
|更新时间:2025-12-08
|
Breaking and Simulation Method of Arrestors Step-by-step Operating of High Voltage DC Circuit Breaker
Vol. 43, Issue 4, Pages: 1079-1085(2017)
作者机构:
1. 华北电力大学电气与电子工程学院
2. 全球能源互联网研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 April 2017,
Published:2017
稿件说明:
移动端阅览
WU Xueguang, WANG Xiaochen, ZHU Yongqiang, et al. Breaking and Simulation Method of Arrestors Step-by-step Operating of High Voltage DC Circuit Breaker[J]. 2017, 43(4): 1079-1085.
DOI:
WU Xueguang, WANG Xiaochen, ZHU Yongqiang, et al. Breaking and Simulation Method of Arrestors Step-by-step Operating of High Voltage DC Circuit Breaker[J]. 2017, 43(4): 1079-1085.DOI:
Breaking and Simulation Method of Arrestors Step-by-step Operating of High Voltage DC Circuit Breaker
摘要
为降低直流电网中故障电流峰值大小
基于一种无弧分断高压直流断路器
首先分析了避雷器的保护原理以及快速机械开关的分断原理;然后针对快速机械开关分断时间较长的问题
提出了一种避雷器分步投入分断方法
在快速机械开关分断达到相应耐压要求后立即投入相应数量避雷器
从而降低了高压直流断路器故障电流峰值大小
减小了系统中关键设备所受的电流应力
并减少了避雷器吸收的能量及其受到的冲击电流热效应;最后通过PSCAD/EMTDC仿真分析
验证了该分断方法的有效性。
Abstract
To reduce the peak value of fault current of DC power grid
we introduced a high voltage DC circuit breaker that could break short fault without arc
and analyzed the principle of arrester and fast mechanical switch. Then
we proposed a new breaking method to solve the problem of relatively long duration of fast mechanical switch breaking. The arrestors that immediately operate mechanical switch can meet the demands of voltage withstanding capacity; the method reduces the peak value of fault current and stress endured by key equipment in system
besides the energy absorbed by arrestors is lowered and thermal effect caused by impulse current is minimized. Finally
the simulation results in PSCAD/EMTDC show that the proposed breaking method is effective.