Elaborate Method for Analyzing Shielding Lightning Performance of 500 k V Tension Tower in Compact Transmission Line
|更新时间:2025-12-08
|
Elaborate Method for Analyzing Shielding Lightning Performance of 500 k V Tension Tower in Compact Transmission Line
Vol. 43, Issue 8, Pages: 2746-2753(2017)
作者机构:
1. 南瑞集团公司(国网电力科学研究院)
2. 国网电力科学研究院武汉南瑞有限责任公司
3. 云南电网有限责任公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2017,
Published:2017
稿件说明:
移动端阅览
赵淳, 任华, 黄修乾, et al. Elaborate Method for Analyzing Shielding Lightning Performance of 500 k V Tension Tower in Compact Transmission Line[J]. 2017, 43(8): 2746-2753.
DOI:
赵淳, 任华, 黄修乾, et al. Elaborate Method for Analyzing Shielding Lightning Performance of 500 k V Tension Tower in Compact Transmission Line[J]. 2017, 43(8): 2746-2753.DOI:
Elaborate Method for Analyzing Shielding Lightning Performance of 500 k V Tension Tower in Compact Transmission Line
The structure of head of 500 k V tension tower of compact transmission line is complex
and shielding failure trip-out rate of this kind of tower cannot be calculated precisely by traditional calculation method. By establishing an elaborate model of 500 k V tension tower of compact transmission line
we proposed an analysis method of lightning shielding failure trip-out rate of tension tower of compact transmission line on the basis of analysis method of whole span lightning shielding performance
and researched the shielding failure trip-out rate of this kind of tower before and after dismantling ground wire branch. The analysis results show that
after ground wire branch being demolished
the shielding failure trip-out rate of the tower will increase by about 16.3%. Therefore
tower lateral rod is proposed to improve lightning shielding performance. The research results indicate that installing tower lateral rod can notably lower the lightning shielding failure trip-out rate of the tower. Moreover
when three tower lateral rods are respectively installed in three jumper cross arms
the shielding failure trip-out rate of the tower can be lowered by about 59.25%. The research results will provide valuable references for lightning protection renovation on 500 k V tension tower of compact transmission line in China.