Electrical Requirements for Ground Wire Insulator and Parallel Discharge Clearance During Insulation Reconstruction for OPGW DC De-icing
|更新时间:2025-12-08
|
Electrical Requirements for Ground Wire Insulator and Parallel Discharge Clearance During Insulation Reconstruction for OPGW DC De-icing
Vol. 43, Issue 8, Pages: 2733-2738(2017)
作者机构:
1. 中国电力科学研究院
2. 国网江苏省电力公司常州供电公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2017,
Published:2017
稿件说明:
移动端阅览
CHEN Xiujuan, XIA Chao, ZHU Haiyu, et al. Electrical Requirements for Ground Wire Insulator and Parallel Discharge Clearance During Insulation Reconstruction for OPGW DC De-icing[J]. 2017, 43(8): 2733-2738.
DOI:
CHEN Xiujuan, XIA Chao, ZHU Haiyu, et al. Electrical Requirements for Ground Wire Insulator and Parallel Discharge Clearance During Insulation Reconstruction for OPGW DC De-icing[J]. 2017, 43(8): 2733-2738.DOI:
Electrical Requirements for Ground Wire Insulator and Parallel Discharge Clearance During Insulation Reconstruction for OPGW DC De-icing
In order to satisfy the demands of DC de-icing of optical fiber composite overhead ground wire(OPGW) and solve questions such as circulating current loss and its liability in suffering from lightning stroke and broken
the grounding method of OPGW must be changed from the current commonly-used method of being grounded at every towers to being grounded at one tower. OPGW would be connected with tower by ground wire insulator
which should be equipped with protective discharge clearance. Consequently
we put forward an idea that the clearance distance should not only satisfy the requirements of withstanding the induced voltage and the de-icing voltage
but also ensure reliable breakdown at lightning voltage. Moreover
we calculated and experimentally researched the electrical characteristics of discharge clearance at normal operation
on de-icing
and in lightning conditions
respectively. Results indicate that discharge clearance should be set from 20 to 100 mm to withstand power frequency induction voltage. Furthermore
discharge clearance should be set more than 60 mm to withstand DC de-icing voltage
which is-22 k V at most. Considering the dispersion of clearance discharge
the clearance should be appropriately increased. The recommended value of discharge clearance is from 70 to 80 mm. The lightning impulse discharge voltage of such clearance is generally not more than 100 k V. However
as transmission line is struck by lightning
overvoltage on insulator and clearance is 885 k V at least
even up to a few MV. Clearance can be broken down reliably to ensure safety of insulator. Research results can provide a theoretical support and data support for OPGW de-icing insulation reconstruction.