Influence of Neutral-point Voltage Deviation of PWM Rectifier on Insulation Monitoring in Small Current Neutral Grounding System
|更新时间:2025-12-08
|
Influence of Neutral-point Voltage Deviation of PWM Rectifier on Insulation Monitoring in Small Current Neutral Grounding System
Vol. 43, Issue 8, Pages: 2620-2629(2017)
作者机构:
1. 解放军理工大学国防工程学院
2. 国防科学技术大学机电工程与自动化学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2017,
Published:2017
稿件说明:
移动端阅览
YAN Jun, WANG Jinquan, XU Ye, et al. Influence of Neutral-point Voltage Deviation of PWM Rectifier on Insulation Monitoring in Small Current Neutral Grounding System[J]. 2017, 43(8): 2620-2629.
DOI:
YAN Jun, WANG Jinquan, XU Ye, et al. Influence of Neutral-point Voltage Deviation of PWM Rectifier on Insulation Monitoring in Small Current Neutral Grounding System[J]. 2017, 43(8): 2620-2629.DOI:
Influence of Neutral-point Voltage Deviation of PWM Rectifier on Insulation Monitoring in Small Current Neutral Grounding System
The three-phase voltage source PWM rectifier(VSR) is key equipment in connecting the distributed generators to the small-current neutral grounding system. So
we have analyzed the frequency disturbance of the switching function as well as the change of positive-pole/negative-pole insulation for the DC side of VSR. The results demonstrate that the neutral-point voltage deviation(NPVD) of the three-phase VSR is a crucial factor which affects the response of insulation monitoring device(IMD). Thus
a pair of methods that take the mean and spectra of the neutral-point voltage as the characteristics
are proposed to detect the NPVD
one is adopted to detect the mean value of the neutral-point voltage based on DC signal injection
and the other one is adopted to determine the frequency disturbance of the neutral-point voltage based on Duffing oscillator. So
the detection result for NPVD is obtained by the variety of the characteristics mentioned above
which is induced by the deviation of the neutral-point voltage. The test results demonstrate that the neutral point deviation caused by the change of DC-side insulation balancing is the primary factor which distorts the detection of insulation resistance; the relative error of detection results obtained by IMD is less than 4% under normal condition
and the relative error is no less than 41% while the neutral point deviation occurs. Further
the test results certify the feasibility of the proposed method
which can be used for improving the response precision of IMD.