Thermal Aging of the Fluorescence Optical Fiber Temperature Sensor Sheath Materials in Transformer Oil
|更新时间:2025-12-08
|
Thermal Aging of the Fluorescence Optical Fiber Temperature Sensor Sheath Materials in Transformer Oil
Vol. 43, Issue 8, Pages: 2599-2607(2017)
作者机构:
1. 国网河北省电力公司电力科学研究院
2. 上海交通大学电气工程系
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2017,
Published:2017
稿件说明:
移动端阅览
GAO Shuguo, GAO Jun, PAN Jing, et al. Thermal Aging of the Fluorescence Optical Fiber Temperature Sensor Sheath Materials in Transformer Oil[J]. 2017, 43(8): 2599-2607.
DOI:
GAO Shuguo, GAO Jun, PAN Jing, et al. Thermal Aging of the Fluorescence Optical Fiber Temperature Sensor Sheath Materials in Transformer Oil[J]. 2017, 43(8): 2599-2607.DOI:
Thermal Aging of the Fluorescence Optical Fiber Temperature Sensor Sheath Materials in Transformer Oil
a fluorescence optical fiber temperature sensor sheath will inevitably degrade in power transformer. According to electrostatic simulation results
the sensor and its sheath normally endures a quiet small electric force. Thus
thermal aging is the main factor influencing the insulation performance of the sheath during long working time. In this study
the fluorescence optical fiber temperature sensor sheaths made of three kinds of materials
such as cross-linked polyolefin
polyurethane and polyvinyl chloride
were subjected in hot transformer oil to degrade. The Fourier transform infrared spectroscopy(FTIR) experiments were used to explore the chemical structure of the sheaths. Moreover
the sheath insulation conditions were estimated based on the mechanical tensile test and the isothermal relaxation current test using a setup of surface electrodes. The FTIR results show that the cross-linked polyolefin and polyurethane sheaths may decompose after aging in transformer oil
whereas no obvious change of polyvinyl chloride sheath is observed. The tensile tests results manifest that the tensile strength and the elongation of cross-linked polyolefin sheath decrease dramatically. The elongation of polyurethane sheath decreases whereas the tensile strength increases with the increase of aging time. However
the elongation and the tensile strength of polyvinyl chloride sheath do not change much after aging. The isothermal relaxation current results demonstrate that the aging factor of aged sheath is larger than that of non-aged sheath. To sum up
the performances in hot transformer oil of different sheaths can be evaluated. The cross-linked polyolefin sheath is the worst
and the anti-aging characteristic of polyurethane sheath is better than cross-linked polyolefin sheath. The polyvinyl chloride sheath is the best.