Influence of the Ingress of Moisture on Electric Characteristic of Oil-immigrated Paper Bushings
|更新时间:2025-12-08
|
Influence of the Ingress of Moisture on Electric Characteristic of Oil-immigrated Paper Bushings
Vol. 43, Issue 8, Pages: 2592-2598(2017)
作者机构:
1. 华北电力大学新能源电力系统国家重点实验室
2. 华北电力大学高电压与电磁兼容北京市重点实验室
3. 中国南方电网科学研究院有限责任公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2017,
Published:2017
稿件说明:
移动端阅览
QI Bo, DAI Quanmin, ZHUO Ran, et al. Influence of the Ingress of Moisture on Electric Characteristic of Oil-immigrated Paper Bushings[J]. 2017, 43(8): 2592-2598.
DOI:
QI Bo, DAI Quanmin, ZHUO Ran, et al. Influence of the Ingress of Moisture on Electric Characteristic of Oil-immigrated Paper Bushings[J]. 2017, 43(8): 2592-2598.DOI:
Influence of the Ingress of Moisture on Electric Characteristic of Oil-immigrated Paper Bushings
In order to study the electrical characteristics of ingress of moisture on oil-immigrated paper(OIP) bushing
OIP bushing models were made and the moisture conditions were simulated by ultrasonic humidifier. The parameters of moisture in oil
partial discharge
and tanδ were measured after the bushing model damped at different time. It is indicated that the moisture in oil firstly increases and then decreases by the standing time of damped bushing
which is classified by the moisture in oil 20 mg/L as three stages: "low-moisture stage
high-moisture stage and moisture migration to paper stage". All of three stages
the curve of tanδ-U trends to increase. Therefore
the possibility of misjudgment for moisture bushing in the low-moisture stage may be obtained by traditional measurement. For the suspicious moisture bushing
the maximum value of Δtanδ under the voltage of 2Um/1.732(Um is the maximum opreation voltage of the equipment) should be lower than 0.2% for the high sensitivity of moisture bushing. Therefore
the insulation condition of OIP bushing can be judged by measuring the curve of tanδ-U and partial discharge so as to find out the moisture bushing earily.